Difference between revisions of "Breaker Panels"

From i3Detroit
Jump to: navigation, search
(Additional information about office subpanel)
(Update for failed breaker)
 
(38 intermediate revisions by 5 users not shown)
Line 1: Line 1:
'''Office Subpanel on South Wall of Shop Area'''<br>
+
'''Office Subpanel on South Wall of Shop Area'''
(Service from 100A breaker above main disconnect, next to water heater)<br>
+
 
 +
<blockquote style="background-color: lightgrey; border: solid thin grey; float: right; padding: 10px">{{QRcodeForThisPage}}</blockquote>
 +
 
 +
(Service from 100A breaker above main disconnect, next to water heater)
 +
 
 
(Federal Pacific, use NA-NI or NC-NI breakers)
 
(Federal Pacific, use NA-NI or NC-NI breakers)
  
Line 14: Line 18:
 
| N/A
 
| N/A
 
| 15
 
| 15
| Office plugs middle
+
| E-room east bench plugs, west hallway plug, men's room plug
 
| Sheathed cable into joist above office
 
| Sheathed cable into joist above office
 
|-
 
|-
Line 20: Line 24:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Office plugs east
+
| Crafts room east and south wall plugs, hallway plug between kitchen and bathroom, kitchen plugs on south wall but not on light switch
 
| Sheathed cable into joist above office
 
| Sheathed cable into joist above office
 
|-  
 
|-  
Line 26: Line 30:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Tree House
+
| Plugs on pillar between south woodshop and tool crib, lower plug on pillar north of tree house
| Through pipe in floor
+
| Through pipe in floor past Tree House
 
|-  
 
|-  
 
| 3
 
| 3
 
| N/A
 
| N/A
 
| 15
 
| 15
| Office lights and emergency exit
+
| Hallway emergency exit light, hallway light inside front door, kitchen lights and plug on light switch, crafts room light
 
| Sheathed cable into joist above office
 
| Sheathed cable into joist above office
 
|-
 
|-
Line 38: Line 42:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Tree House
+
| Tree House plug on southeast corner pillar (bell is connected), three plugs on horizontal beam on west side of Tree House
 
| Through pipe in floor
 
| Through pipe in floor
 
|-
 
|-
Line 44: Line 48:
 
| N/A
 
| N/A
 
| 15
 
| 15
| Office lights middle
+
| Fab room lights, e-room lights, e-room west bench plugs and west wall plug, bathroom lights and plug, men's room light
 
| Sheathed cable into joist above office
 
| Sheathed cable into joist above office
 
|-
 
|-
Line 50: Line 54:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Bathroom office heat/fan
+
| Bathroom heat/fan
 
| Sheathed cable into joist above office
 
| Sheathed cable into joist above office
 
|-
 
|-
Line 56: Line 60:
 
| N/A
 
| N/A
 
| 15
 
| 15
| Shop lights
+
| Shop lights (mid-east)
| One of two switches left of breaker panel, to junction box next to SE furnace
+
| Leftmost of two switches left of breaker panel, to mid-east junction box
 
|-
 
|-
 
| 9
 
| 9
 
| N/A
 
| N/A
 
| 15
 
| 15
| Shop lights middle
+
| Shop lights over commons tables (near-east)
| Lower switch left of breaker panel, to east ceiling junction box
+
| Lower switch left of breaker panel, to near-east junction box
 
|-
 
|-
 
| 10
 
| 10
 
| N/A
 
| N/A
 
| 20
 
| 20
| Office lights and plugs
+
| IT shelf over front door, east shop ceiling fans, lights at main door, emergency exit lights at main door, kitchen plugs on north and east walls
| Lights overhead door emergency exit (into office wall left of breaker panel)
+
| Conduit into office wall left of breaker panel
 
|-
 
|-
 
| 11
 
| 11
 
| N/A
 
| N/A
 
| 15
 
| 15
| Shop lights east
+
| Shop lights (far-east)
| One of two switches left of breaker panel, to junction box next to SE furnace
+
| Rightmost of two switches left of breaker panel, to mid-east junction box
 
|-
 
|-
 
| 12
 
| 12
 
| N/A
 
| N/A
 
| 20
 
| 20
| Shop plugs east wall
+
| Shop plugs on east wall (welding shop, tool crib)
| Through pipe in floor, power for IT components over front door
+
| Through pipe in floor
 
|-
 
|-
 
| 13
 
| 13
 
| N/A
 
| N/A
 
| 15
 
| 15
| Leave Off
+
| North shop furnaces
| To junction box next to SE furnace (switched on as of 2011-06-07)
+
| To near-east junction box
 
|-
 
|-
| 14
+
| 14, 16
| 16
+
| 18, 20
 
| 40
 
| 40
 
| Rooftop AC and heat
 
| Rooftop AC and heat
| To east loft, including roof
+
| To east loft junction box, then to roof
 
|-
 
|-
 
| 15
 
| 15
 
| N/A
 
| N/A
 
| 15
 
| 15
| Heater south
+
| Commons tables cord reels
| To east ceiling junction box (switched off as of 2011-06-07)
+
| To near-east junction box
 
|-
 
|-
 
| 17
 
| 17
 
| N/A
 
| N/A
 
| 15
 
| 15
|  
+
| Plug over commons area: exhaust fan for Fab Lab, outlet strips for Tree House
| To east ceiling junction box
+
| To near-east junction box
|-
+
| 18
+
| 20
+
| 40
+
|
+
| To east loft, including roof
+
 
|-
 
|-
 
| 19
 
| 19
 
| N/A
 
| N/A
 
| 15
 
| 15
| Leave Off
+
| Big light over Haas CNC
| To junction box next to SE furnace (switched off as of 2011-06-07)
+
| To mid-east junction box
 
|-
 
|-
 
| 21a
 
| 21a
 
| N/A
 
| N/A
 
| 15
 
| 15
| Heater overhead door
+
| South-east shop furnace
| To east ceiling junction box
+
| To mid-east junction box
 
|-
 
|-
 
| 21b
 
| 21b
 
| N/A
 
| N/A
 
| 20
 
| 20
| Office plugs east
+
| Unknown
| To west loft (upper pipe)
+
| To west loft/attic (lower knockout)
 
|-
 
|-
 
| 22a
 
| 22a
 
| N/A
 
| N/A
 
| 15
 
| 15
| Outlet left of breaker panel
 
 
| IT server rack power
 
| IT server rack power
 +
| Plug left of breaker panel
 
|-
 
|-
 
| 22b
 
| 22b
 
| N/A
 
| N/A
 
| 20
 
| 20
|  
+
| Not used
| To east loft, including roof
+
| To east loft junction boxes
 
|-
 
|-
 
| 23a
 
| 23a
 
| N/A
 
| N/A
 
| 20
 
| 20
|  
+
| Unknown
| To west loft (upper pipe)
+
| To west loft/attic (lower knockout)
 
|-
 
|-
 
| 23b
 
| 23b
 
| N/A
 
| N/A
 
| 20
 
| 20
|  
+
| H-structure and cord reel just south of it
| To east ceiling junction box
+
| To near-east junction box
 
|-
 
|-
 
| 24
 
| 24
 
| N/A
 
| N/A
 
| 20
 
| 20
| Office lights and plugs
+
| Hallway lights (except light inside front door)
| To west loft (lower pipe)
+
| To west loft (upper knockout)
 
|}
 
|}
  
Line 184: Line 182:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Water cooler plug
+
| Shop plug next to Utilatub, switch to SW roof vent
 
|  
 
|  
 
|-
 
|-
Line 190: Line 188:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Shop fans (leave on so pipes don't freeze)
+
| West shop ceiling fan, shop plug under west loft, fab lab plugs
 
|  
 
|  
 
|-
 
|-
Line 196: Line 194:
 
| N/A
 
| N/A
 
| 15
 
| 15
| Rear shop lights
+
| Rear shop lights, overhead power cord near utilitub, upper plug above fire ext on mid-shop pillar
|
+
| No light switch
 
|-
 
|-
 
| 6
 
| 6
 
| N/A
 
| N/A
 
| 20
 
| 20
| West shop lights
+
| Not used
 
|  
 
|  
 
|-
 
|-
Line 208: Line 206:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Emergency lights, night lights
+
| West shop emergency lights, west shop night lights
 
|
 
|
 
|-
 
|-
Line 214: Line 212:
 
| N/A
 
| N/A
 
| 20
 
| 20
| West shop lights
+
| West shop lights, Tree House lights
|
+
| No light switch
 
|-
 
|-
| 9a
+
| 9
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plug on wall shop by water cooler
+
| South shop wall plug next to broom rack
 
|
 
|
 
|-
 
|-
Line 226: Line 224:
 
| N/A
 
| N/A
 
| 20
 
| 20
| West shop lights
+
| West shop lights, Tree House lights
|  
+
| No light switch
 
|-
 
|-
 
| 11
 
| 11
 
| N/A
 
| N/A
| N/A
+
| 30
| Spare
+
| IT Rack UPS
| No breaker installed
+
|  
 
|-
 
|-
 
| 12
 
| 12
Line 245: Line 243:
 
| 60
 
| 60
 
| Subpanel in rear shop
 
| Subpanel in rear shop
|  
+
| Breaker replaced in April 2013
 
|}
 
|}
  
Line 276: Line 274:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on west wall
+
| Shop plugs on west wall behind sheet-goods and user storage areas
 
|  
 
|  
 
|-
 
|-
Line 282: Line 280:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on north wall
+
| Wire capped off in wall junction box next to user storage rack
 
|  
 
|  
 
|-
 
|-
Line 288: Line 286:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on west wall
+
| Plugs on north wall in western end of metal shop and on metal shop ceiling
|
+
| Through handy box over woodshop/metalshop doorway
 
|-
 
|-
 
| 5b
 
| 5b
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on east wall
+
| Wire capped off in wall junction box next to user storage rack
|
+
| Breaker appears to have failed; cannot be turned on
 
|-
 
|-
 
| 6
 
| 6
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on west wall
+
| West shop wall, six southernmost plugs
|  
+
| Breaker was replaced on 01-20-2014
 
|-
 
|-
 
| 7
 
| 7
 
| N/A
 
| N/A
 
| 20
 
| 20
|
+
| Wood shop plugs on north wall and plug next to breaker panel.
 
|
 
|
 
|-
 
|-
Line 312: Line 310:
 
| N/A
 
| N/A
 
| 20
 
| 20
| Lights in NE rear
+
| Plug near surface grinder, metal shop lights
|
+
| Through handy box over woodshop/metalshop doorway
 
|-
 
|-
 
| 8b
 
| 8b
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs on NE wall
+
| Plugs on north wall in eastern end of metal shop
|
+
| Conduit along north wall in loft
 
|-
 
|-
 
| 9
 
| 9
Line 331: Line 329:
 
| 20
 
| 20
 
| Roof exhaust next to beam
 
| Roof exhaust next to beam
|  
+
| Through handy box over woodshop/metalshop doorway
 
|-
 
|-
 
| 12
 
| 12
 
| N/A
 
| N/A
 
| 20
 
| 20
| Plugs north by door NE
+
| Plugs for drill press and tool grinders, plugs under north wall clock
|
+
| Through handy box over woodshop/metalshop doorway
 
|}
 
|}
  
 
<br>
 
<br>

Latest revision as of 10:51, 5 April 2014

Office Subpanel on South Wall of Shop Area

(Service from 100A breaker above main disconnect, next to water heater)

(Federal Pacific, use NA-NI or NC-NI breakers)

Location Second Pole Amperes Description Notes
1a N/A 15 E-room east bench plugs, west hallway plug, men's room plug Sheathed cable into joist above office
1b N/A 20 Crafts room east and south wall plugs, hallway plug between kitchen and bathroom, kitchen plugs on south wall but not on light switch Sheathed cable into joist above office
2 N/A 20 Plugs on pillar between south woodshop and tool crib, lower plug on pillar north of tree house Through pipe in floor past Tree House
3 N/A 15 Hallway emergency exit light, hallway light inside front door, kitchen lights and plug on light switch, crafts room light Sheathed cable into joist above office
4 N/A 20 Tree House plug on southeast corner pillar (bell is connected), three plugs on horizontal beam on west side of Tree House Through pipe in floor
5 N/A 15 Fab room lights, e-room lights, e-room west bench plugs and west wall plug, bathroom lights and plug, men's room light Sheathed cable into joist above office
6,8 N/A 20 Bathroom heat/fan Sheathed cable into joist above office
7 N/A 15 Shop lights (mid-east) Leftmost of two switches left of breaker panel, to mid-east junction box
9 N/A 15 Shop lights over commons tables (near-east) Lower switch left of breaker panel, to near-east junction box
10 N/A 20 IT shelf over front door, east shop ceiling fans, lights at main door, emergency exit lights at main door, kitchen plugs on north and east walls Conduit into office wall left of breaker panel
11 N/A 15 Shop lights (far-east) Rightmost of two switches left of breaker panel, to mid-east junction box
12 N/A 20 Shop plugs on east wall (welding shop, tool crib) Through pipe in floor
13 N/A 15 North shop furnaces To near-east junction box
14, 16 18, 20 40 Rooftop AC and heat To east loft junction box, then to roof
15 N/A 15 Commons tables cord reels To near-east junction box
17 N/A 15 Plug over commons area: exhaust fan for Fab Lab, outlet strips for Tree House To near-east junction box
19 N/A 15 Big light over Haas CNC To mid-east junction box
21a N/A 15 South-east shop furnace To mid-east junction box
21b N/A 20 Unknown To west loft/attic (lower knockout)
22a N/A 15 IT server rack power Plug left of breaker panel
22b N/A 20 Not used To east loft junction boxes
23a N/A 20 Unknown To west loft/attic (lower knockout)
23b N/A 20 H-structure and cord reel just south of it To near-east junction box
24 N/A 20 Hallway lights (except light inside front door) To west loft (upper knockout)


Panel in SW Corner of Shop Area
(Pushmatic Electri-Center)

Location Second Pole Amperes Description Notes
1 2 100 Main
3 N/A 20 Shop plug next to Utilatub, switch to SW roof vent
4 N/A 20 West shop ceiling fan, shop plug under west loft, fab lab plugs
5 N/A 15 Rear shop lights, overhead power cord near utilitub, upper plug above fire ext on mid-shop pillar No light switch
6 N/A 20 Not used
7 N/A 20 West shop emergency lights, west shop night lights
8 N/A 20 West shop lights, Tree House lights No light switch
9 N/A 20 South shop wall plug next to broom rack
10 N/A 20 West shop lights, Tree House lights No light switch
11 N/A 30 IT Rack UPS
12 N/A N/A Spare No breaker installed
13 14 60 Subpanel in rear shop Breaker replaced in April 2013


Subpanel in NW Corner of Shop Area
(Resembles Pushmatic Electri-Center)

Location Second Pole Amperes Description Notes
1 N/A N/A Spare No breaker installed
2 N/A N/A Spare No breaker installed
3 N/A 20 Shop plugs on west wall behind sheet-goods and user storage areas
4 N/A 20 Wire capped off in wall junction box next to user storage rack
5a N/A 20 Plugs on north wall in western end of metal shop and on metal shop ceiling Through handy box over woodshop/metalshop doorway
5b N/A 20 Wire capped off in wall junction box next to user storage rack Breaker appears to have failed; cannot be turned on
6 N/A 20 West shop wall, six southernmost plugs Breaker was replaced on 01-20-2014
7 N/A 20 Wood shop plugs on north wall and plug next to breaker panel.
8a N/A 20 Plug near surface grinder, metal shop lights Through handy box over woodshop/metalshop doorway
8b N/A 20 Plugs on north wall in eastern end of metal shop Conduit along north wall in loft
9 10 20 Roof exhaust fans
11 N/A 20 Roof exhaust next to beam Through handy box over woodshop/metalshop doorway
12 N/A 20 Plugs for drill press and tool grinders, plugs under north wall clock Through handy box over woodshop/metalshop doorway